CVE ID
|
CWE ID
|
# of Exploits
|
Vulnerability Type(s)
|
Publish Date
|
Update Date
|
Score
|
Gained Access Level
|
Access
|
Complexity
|
Authentication
|
Conf.
|
Integ.
|
Avail.
|
1 |
CVE-2014-4686 |
|
|
+Info |
2014-07-24 |
2014-07-25 |
6.8 |
None |
Remote |
Medium |
Not required |
Partial |
Partial |
Partial |
The Project administration application in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, has a hardcoded encryption key, which allows remote attackers to obtain sensitive information by extracting this key from another product installation and then employing this key during the sniffing of network traffic on TCP port 1030. |
2 |
CVE-2014-4685 |
264 |
|
+Priv |
2014-07-24 |
2014-07-25 |
4.6 |
None |
Local |
Low |
Not required |
Partial |
Partial |
Partial |
Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows local users to gain privileges by leveraging weak system-object access control. |
3 |
CVE-2014-4684 |
264 |
|
+Priv |
2014-07-24 |
2014-07-25 |
6.0 |
None |
Remote |
Medium |
??? |
Partial |
Partial |
Partial |
The database server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a request to TCP port 1433. |
4 |
CVE-2014-4683 |
264 |
|
+Priv |
2014-07-24 |
2014-07-25 |
4.9 |
None |
Remote |
Medium |
??? |
Partial |
Partial |
None |
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a (1) HTTP or (2) HTTPS request. |
5 |
CVE-2014-4682 |
200 |
|
+Info |
2014-07-24 |
2014-07-25 |
5.0 |
None |
Remote |
Low |
Not required |
Partial |
None |
None |
The WebNavigator server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote attackers to obtain sensitive information via an HTTP request. |
6 |
CVE-2013-0679 |
22 |
|
Dir. Trav. |
2013-03-21 |
2013-03-22 |
4.0 |
None |
Remote |
Low |
??? |
Partial |
None |
None |
Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
7 |
CVE-2013-0677 |
200 |
|
DoS +Info |
2013-03-21 |
2013-03-22 |
5.8 |
None |
Remote |
Medium |
Not required |
Partial |
None |
Partial |
The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. |
8 |
CVE-2013-0676 |
264 |
|
+Info |
2013-03-21 |
2013-03-22 |
4.0 |
None |
Remote |
Low |
??? |
Partial |
None |
None |
Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly assign privileges for the database containing WebNavigator credentials, which allows remote authenticated users to obtain sensitive information via a SQL query. |
9 |
CVE-2013-0675 |
119 |
|
DoS Overflow |
2013-03-21 |
2013-03-22 |
6.1 |
None |
Local Network |
Low |
Not required |
None |
None |
Complete |
Buffer overflow in CCEServer (aka the central communications component) in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to cause a denial of service via a crafted packet. |
10 |
CVE-2013-0674 |
119 |
|
Exec Code Overflow |
2013-03-21 |
2013-03-22 |
6.8 |
None |
Remote |
Medium |
Not required |
Partial |
Partial |
Partial |
Buffer overflow in the RegReader ActiveX control in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to execute arbitrary code via a long parameter. |
11 |
CVE-2012-3034 |
200 |
|
+Info |
2012-09-18 |
2012-09-19 |
4.3 |
None |
Remote |
Medium |
Not required |
Partial |
None |
None |
WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to discover a username and password via crafted parameters to unspecified methods in ActiveX controls. |
12 |
CVE-2012-3032 |
89 |
|
Exec Code Sql |
2012-09-18 |
2012-09-19 |
7.5 |
None |
Remote |
Low |
Not required |
Partial |
Partial |
Partial |
SQL injection vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to execute arbitrary SQL commands via a crafted SOAP message. |
13 |
CVE-2012-3031 |
79 |
|
XSS |
2012-09-18 |
2012-09-19 |
4.3 |
None |
Remote |
Medium |
Not required |
None |
Partial |
None |
Multiple cross-site scripting (XSS) vulnerabilities in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allow remote attackers to inject arbitrary web script or HTML via a (1) GET parameter, (2) POST parameter, or (3) Referer HTTP header. |
14 |
CVE-2012-3030 |
264 |
|
|
2012-09-18 |
2012-12-20 |
5.0 |
None |
Remote |
Low |
Not required |
Partial |
None |
None |
WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, stores sensitive information under the web root with insufficient access control, which allows remote attackers to read a (1) log file or (2) configuration file via a direct request. |
15 |
CVE-2012-3028 |
352 |
|
DoS CSRF |
2012-09-18 |
2012-09-19 |
6.8 |
None |
Remote |
Medium |
Not required |
Partial |
Partial |
Partial |
Cross-site request forgery (CSRF) vulnerability in WebNavigator in Siemens WinCC 7.0 SP3 and earlier, as used in SIMATIC PCS7 and other products, allows remote attackers to hijack the authentication of arbitrary users for requests that modify data or cause a denial of service. |